Why is the best use of high - lying battery, low battery is best to use vertical?
Answer: high battery vertially easily lead to internal battery electrolyte stratification, placed a long time, the density of sulfate upper thinning, lower sulfate density thicken, thus forming a concentration micro battery, so long cause the battery self discharge, shorten the service life of the battery.
The possibility of low battery electrolyte stratification is much smaller, and the use of vertical discharge will effectively reduce the possibility of leakage of the battery, so the battery should be selected to establish a low profile.
How to determine the installation of the battery?
Answer: for the use of AGM technology valve control battery, high - type design of the battery should be installed in the installation of horizontal lying, so as to avoid the use of electrolyte stratification. When installed, the main consideration of the installation area and ground bearing, the user can choose according to the battery placed installation two layer, four layer and eight layer, the ground bearing condition, select four or eight layers of installation can save area, this method is suitable for the battery in a building or underground there is enough room, the area and the ground bearing ability is poor, should adopt two layer mode of installation. Refer to the installation manual". Beyond the "installation manual", the company's technical staff to carry out special design for customers, also known as special design.